Nordichooldus · NVAC OÜ · Tallinn and Harju County+372 5619 7399
Nordichooldus.ee Request a quote

VENTILATION AND AIR CONDITIONING GUIDES

Ventilation diagnostics and airflow measurement

Diagnostics identify the cause before ordering parts or extra work. Maintenance, measurement and repair are different tasks.

When might routine maintenance be insufficient?

Diagnostics are appropriate for recurring alarms, sudden airflow changes, a stuffy room or a new noise. They may also be needed after replacement or duct changes. Changing a filter does not establish that sensors, fans or controls work correctly.

Before the visit, send the model, alarm photo and problem history. If it happens only in certain weather or at certain times, this helps identify links to outdoor air, schedules or other equipment.

What should an inspection include?

  • Compare alarms and event history with the correct manual.
  • Check filters, accessible air paths and visible unit condition.
  • Review settings and possible building control commands.
  • Measure room supply and extract airflow where needed.
  • Document defects, measurements and further work.

Scope depends on model and access. Quotes should separate initial checks, measurements, adjustments and repairs. Parts and electrical work are not automatically included.

Why does fan speed percentage not prove balance?

Equal fan speed percentages do not guarantee equal airflow because air path resistance can differ. A displayed total flow does not prove each bedroom receives its design airflow. Measurements must account for clean filters, operating mode and system design data.

Airobot’s manual distinguishes conventional fan adjustment from constant airflow control on newer units. Identify the unit’s capabilities before adjusting. Automatic total flow control does not replace room air distribution checks.

In apartment buildings, involve the shared system manager

Changes in one apartment can affect others on a shared system. Do not connect a hood to a shared shaft or change rooftop fan settings without an agreed solution. Notify the association if backdraught or odours occur in several apartments. Read about apartment building ventilation maintenance.

What should the inspection produce?

A useful report separates measured facts from assumptions. Ask which mode was measured, what deviations were found and what will resolve them. Missing designs or previous measurements should be recorded as limitations. Recheck the result after repairs where needed.

Official sources

Manufacturer information checked on 8 October 2026. Before taking action, match the manual’s model, controller and revision to your unit. Manuals may subsequently change.

Related reading

Call usRequest a quote